China OEM 3KA Manufacturers –PIN type Polymeric Insulator – HolleyDetail:
Specifications
Features | Unit | VALUE | VALUE | |
PIN TYPE POLYMERIC INSULATOR 13.8 kV | PIN TYPE POLYMERIC INSULATOR 22.9 kV | |||
1 | Operating Voltage(Phase-Phase) | ≤ 13.8 kV | ≥13.8 kV , ≤22.9 kV | |
2 | Insulator model | FPQ-24kV/12kN | FPQ-35kV/12kN | |
3 | Standard | IEC 61952:2008 | IEC 61952:2008 | |
4 | Design and construction features | |||
| Core material (core) | Fiberglass with Fiberglas Round Rod Bar ECR | Fiberglass with Fiberglas Round Rod Bar ECR | ||
| Insulated housing and sheds: | High consistency silicone rubber type HTV or LSR | High consistency silicone rubber type HTV or LSR | ||
| - Resistance to tracking and erosion of insulating material: Silicone rubber | Class 2A, 6 kV (according to IEC 60587) | Class 2A, 6 kV (according to IEC 60587) | ||
| Material of the coupling hardware | Forged steel | Forged steel | ||
| Insulator Head Material | Porcelain | Porcelain | ||
| Galvanization of hardware | According to ASTM A153/A153M, average thickness of 86um | According to ASTM A153/A153M, average thickness of 86um | ||
5 | Electrical Values: | |||
| Operation voltage phase-phase | kV | 10kV , 13.2kV to 13.8kV | 13.8kV to 22.9kV | |
| Maximum voltage for the insulator Um | kV(r.m.s) | 24 | 35 | |
| Nominal frequency | Hz | 60 | 60 | |
| Minimum creepage distance | mm | 645 | 915 | |
| Arcing Distance | mm | 230 | 275 | |
| Sheds diameter | mm | 130/110 | 130/110 | |
| Sheds passage | mm | 22.5 | 22.5 | |
| Withstand voltage at the industrial frequency: | ||||
| -Dry | kV | 80 | 115 | |
| -Wet | kV | 70 | 105 | |
| Impulse Withstand voltage 1.2/50us: | ||||
| -Positive | kV | 150 | 190 | |
| -Negative | kV | 200 | 220 | |
| Low Frequency Test Voltage (RMS to Earth) | kV | 22 | 30 | |
| RIV Maximum at 1000 KHz | Microvolts | 100 | 100 | |
6 | Mechanical values: | |||
| Minimal cantilever strength | kN | 12 | 12 | |
| Compression effort | kN | ≥ 8 | 45 | |
| Weight | kg | 4.3 | ≥8 | |
| Core diameter | mm | 45 | 4.6 | |
| Minimum PIN height | mm | 237 | 130 | |
| Diameter of bolt | mm | 20 | 42 | |
7 | Design tests | According to clause 10 IEC61952 | According to clause 10 IEC61952 | |
8 | Type tests | According to clause 11 IEC61952 | According to clause 11 IEC61952 | |
9 | Sampling tests | According to clause 12 IEC 61952 | According to clause 12 IEC61952 | |
10 | Individual tests | According to clause 13 IEC 61952 | According to clause 13 IEC61952 | |
11 | UV resistance tests | According to ASTM G154 and ASTM G155 or ISO 4892-3 and ISO 16474-3 | According to ASTM G154 and ASTM G155 or ISO 4892-3 and ISO 16474-3 | |
12 | Includes spike | Yes | Yes |
Product detail pictures:

Related Product Guide:
We strive for excellence, service the customers", hopes to become the best cooperation team and dominator enterprise for personnel, suppliers and customers, realizes value share and continuous promotion forChina OEM 3KA Manufacturers –PIN type Polymeric Insulator – Holley, The product will supply to all over the world, such as: Sevilla, Belize, Auckland, Item have passed by means of the national qualified certification and been well received in our main industry. Our expert engineering team will often be ready to serve you for consultation and feedback. We have been able to also deliver you with cost-free samples to meet your specs. Ideal efforts will probably be produced to deliver you the most beneficial service and solutions. Should really you be interested in our company and solutions, please make contact with us by sending us emails or call us straight away. To be able to know our solutions and enterprise. ar more, you'll be able to come to our factory to see it. We will constantly welcome guests from all over the world to our firm. o build business enterprise. elations with us. You should feel absolutely free to speak to us for organization. nd we believe we are going to share the best trading practical experience with all our merchants.